HAI Part Number: RC-80B
Omnistat-Z Model: RC-80BZ
Dimensions: 5.5" W x 3.75" H x 1.1" D
- Single stage heating and cooling systems, non heat pump
- 1 stage heat, 1 stage cool
- Can be set to heat only or cool only
- Can power steal for retrofitting heat/cool systems with only 4 wires
- Adjustable anticipator
- Use for forced air, radiant heat, hydronic heat, steam, electric,
gas, oil, etc.
Omnistat thermostats feature a sleek, modern
case design that blends in with any décor.
The large LCD display with "cool blue"
LCD backlight shows time, temperature and operational mode.
The controls
are easy to use, with simple raise and lower temperature keys, mode (off, heat,
cool, auto) and fan keys (on, auto). The Prog key is used for programming when
the thermostat's internal scheduling features are used. The Hold key maintains
the current settings as long as the hold indicator is on. A "remote"
indicator shows when the thermostat has been set by remote control.
Omnistat thermostats feature
a multi-mode communications interface for connection to many types of home and
building automation systems. This interface allows more comprehensive energy and comfort
management by setting the thermostats based on occupancy and home or building
modes along with traditional scheduling. Two full communications modes are
available for connection to automation systems and personal computers. Two
additional modes are available for simplified connection to most access control,
security and time clock systems.
Omnistat thermostats will work with any of HAI's
Lumina family or Omni family home control systems. When used with an
HAI home control system, full control of Omnistat thermostats is
available on a Console or Keypad, OmniTouch touchscreens, telephones (with voice response)
and over the Internet with Snap-Link or Web-Link II. The HAI home control system's advanced
programming features add
comprehensive energy management capabilities to one or more thermostats. The
HAI home control system automatically sets the thermostat's time and displays the
outdoor temperature when an outdoor sensor (available in
Energy Management Product Line) has been set up.
All Omnistat thermostats feature advanced logic for superior temperature control, including
"anticipation" for maximum comfort.
The installer can set limits on the heat and cool
settings, to prevent the thermostat from being set too high or too low. The
thermostat prevents short cycling, protecting the system's compressor. A
filter reminder tracks running time of the fan, indicating when it is time to
replace the filter.
HAI is an ENERGY STAR® Partner. All Omnistat thermostats meet the Environmental
Protection Agency's ENERGY STAR® Guidelines for energy efficiency.
|
| |
|
Z-Wave™ Model
|
|
The Omnistat-Z version of this thermostat is the RC-80BZ.
It has a built-in Z-Wave™ transceiver, and will
work with any Z-Wave™ network. When connecting it
to an HAI controller, use the Leviton Vizia RF to RS232 Serial Bridge (Leviton
part number RZCOP-1LW).
|
| |
|
FEATURES
|
|
This Omnistat has the following features:
- Large "cool blue" LCD backlight
that displays time, temperature and mode.
-
Selectable Fahrenheit or Celsius display, AM/PM or 24 hour time format
-
Outdoor temperature display (when connected to Omni-family controller and using
outdoor sensor)
- Simple user controls for: Mode, Fan, Set,
Hold, Raise and Lower Temperature.
- Non-volatile program and setting memory: no
batteries required for long term, maintenance-free operation.
- Automatic Changeover between heating and
cooling modes (can be configured for manual changeover if auto is not
desired).
- Heat Only and Cool Only modes.
- Adjustable cycle times.
- Adjustable Anticipator
- System Runtime monitor (this week, last week;
hours).
- Filter Clean/Replace indicator reminds owner
to clean filter to maintain best efficiency and performance.
This reminder is based upon the time the fan has run. It indicates
"Filt" on the display to suggest changing the filter. This reminder is reset
by pressing the Prog key.
- Compatible with systems using 24 volt (20 to
30 V) AC or DC controls.
- 5-1-1 programming capability: Separate
schedules for Weekdays, Saturday and Sunday, with separate heat and cool
settings for morning, day, evening and night. Internal scheduler can be
disabled for use with automation systems.
- High limit for heat setting is adjustable by
installer.
- Low limit for cool setting is adjustable by
installer.
- Has power stealing capability for
retrofitting 4-wire heating and cooling systems, or can use
"common" wire to disable power stealing.
- Energy Star compliant and UL Listed.
|
|
REMOTE COMMUNICATIONS
|
|
This Omnistat has the following remote control features:
- 4 communications modes, selectable during
installation: 2 serial modes for connection to home automation systems,
building management systems and personal computers, and 2 voltage signal
modes for connection to time clocks, remote setback switches and many
burglar alarm panels
- Data signal is electrically isolated from
heating and cooling system for superior reliability in all modes.
Fully interactive with all HAI manufactured controllers, including mode,
heat setting, cool setting, fan and hold settings. (Serial Mode 1)
- Can communicate directly with the RS-232 port
of a personal computer - no adapter
required. Serial mode protocol: addressable up to 127 units, bi-directional,
1 start bit, 8 data bits, 1 stop bit NRZ. 300
baud data rate. Can communicate continuously without loss of function.
Protocol is available from HAI web site. (Serial Mode 2)
- Remote selection between Day and Night
settings: a remote signal (12 VDC) selects between user programmed
"day" and "night" settings for both heating and cooling
modes. The settings can be changed by a user, but they will return to the
preprogrammed ones on application (for night) or removal (for day) of the
signal. Ideal for use with time clocks, building management systems, access
control systems, alarm systems to set to preprogrammed temperatures when
building is unoccupied. (Voltage signal mode 1)
- Thermostat Override: a remote signal (12 VDC)
overrides the thermostat operation and turns off the HVAC system. Removal of
signal restores normal operation. Remote indicator shows that thermostat is
overridden. Safety feature will turn on heat if temperature drops below 45
degrees F. (Voltage signal mode 2)
|
| |
|